Current best sellers

Intumescent Lock Protection

New product

Fire protection for door hinges and closers on fire rated doors.

Supplied in standard sizes to make installation quick and convenient- Protects metalwork on doors for up to 91 minutes.

Intumescent paper cools the lock, hinges, and screws and protects them from overheating in the event of a fire.

Envirograf Product 71

More details

£0.79

- +

 
Product Info

A 1mm thick, flexible, sheet of intumescent material. It is not affected by moisture. It is suitable for use behind hinges, steel door closers and around lock areas which require protection on a fire rated door. When installed the sheet compress without compromising its protective qualities.

Application 

Hinge, Lock and Door Closer Protection:

Hinges: Remove hinges from both door and frame, cut the cut the Envirograf intumescent paper to size to size, sandwich it between hinge and rebate on both door and frame then screw the hinges back.

Lock & Keep:

Remove lock, cut the Envirograf intumescent paper to size, wrap it around the lock and sandwich it between the lock and door as you replace the lock. Place paper under the keep plate as well.

Door Closer:

Before fitting a door closer sandwich pre-cut cut the Envirograf intumescent paper between the closer and the door face then fasten the closer to the door. When ordering state the size of intumescent paper required for your door closer.

 
Fire Performance

This product was used to protect ironmongery in a number of fire resistance tests employing the general procedures and criteria of BS476 Part 22 (1987) without an integrity failure being recorded for up to 91 minutes.

Also tested to EN1634-1 (2000) for 68 minutes.